FieldServer - QuickServer LonWorks BACnet/IP

The FS-QS-1011-0131 QuickServer provides a cost-effective, easy to use interface from LonWorks to BACnet/IP.

 

 


Downloads

Protocol Datasheets

BACnet IP

LonWorks

Gateway Datasheets

QuickServer

Configuration Manuals

BACnet IP

LonWorks


Question/Purchase

  • This gateway can read LonWorks data from your LonWorks devices and publish it as BACnet IP data.
  • It can also write to the LonWorks devices.
  • This gateway can also do the reverse, read BACnet IP data and publish it as LonWorks data.
  • It can also write to the BACnet IP devices.

In summary, this gateway can act as:

Master on the LonWorks network: Hence it is capable of reading data from the various LonWorks slave devices and writing data to them if required.

Slave on the LonWorks network: You can use the gateway in this mode if you have a LonWorks master on the network which would be reading data from the gateway.

Client/Master on the BACnet IP network: Hence it is capable of reading data from the various BACnet IP devices and writing data to them if required.

Server/Slave on the BACnet IP network: The gateway can be configured to be a server of data values, hence another BACnet IP client can read data from the gateway and write data into the gateway.

 

QuickServer Key Features:

  • Ability to interface up to 250 points of common BAS protocols
  • Multi-configuration capability; specific configurations selectable via DIP switches or software
  • Flat panel mount standard, DIN rail mount option
  • DIP switches to select baud rate or node ID on the fly
  • LonMark Certified

LonWorks driver:

  • The FieldServer LonWorks device can be used with explicit and/or implicit addressing and can be bound to a maximum of 15 other LonWorks nodes. The QuickServer can handle a maximum of 250 explicitly addressed nodes. The QuickServer currently supports a default of 63 network variable aliases to avoid network variable connection constraints.
  • QuickServer can transfer data (Network Variables) in two ways
    • It can poll (request data from) other devices at a regular interval
    • It can send Network Variable Updates at a regular interval, when data has changed, or, in throttled mode using maximum and minimum send time and change on delta parameters
  • QuickServer can be configured by Network Management Tools such as LonMaker. For binding (implicit mode), a Network Management Tool is necessary to create the bindings.
  • The External Interface File (.XIF) for the QuickServer can be uploaded from FieldServer for a particular application
  • Driver type: Client or Server
  • Connection type: FTT-10 Free Topology Network Transceiver
  • Data types supported:
    • Integers (Long, short, signed, unsigned)
    • Float
    • Byte
    • Bit

BACnet/IP driver:

  • Driver type: Client or Server
  • Data Link layer: BACnet IP, (Annex J)
  • Connection type: BACnet/IP Internet Protocol (IP), 10/100BaseT, BBMD supported
  • BACnet COV support for fast data communication while reducing traffic over a BACnet network
  • Data types supported:
    • AI - Analog Input Object
    • AO - Analog Output Object
    • AV - Analog Value Object
    • BI - Binary Input Object
    • BO - Binary Output Object
    • BV - Binary Value Object
    • MI - Multi-state Input Object
    • MO - Multi-state Output Object
    • MV - Multi-state Value Object
  • LonWorks is a trademark of Echelon Corporation
  • BACnet is a trademark of ASHRAE

 

How to configure the FieldServer gateway?

-We will configure the gateway for you based on your requirement and support you during commissioning of the gateway, so you do not  have to worry about configuring the FieldServer gateway.

-However, it is very helpful to know how to configure the devices. All the required tools and supporting product manuals with be provided completely free of cost with your purchase.

-Configuration of the FieldServer is done using a '.csv' file. This file can be edited using any text editor (example Microsoft excel).

-In this file we need to enter information for the Client and Server side interfaces of the FieldServer. This includes but is not limited to:

                Node ids of the slave devices

                IP addresses/device address of the slave devices

                Baud rate, parity, stop bits for serial communication

                Scan rates

- And finally we need to create an internal mapping that would map each data value read on the client side to a data value on the server side.

-For detailed information on configuration please get in touch with us and review the configuration manual on top of this page